CERTsSecurity

Unitronics Vision Series PLCs: CVSS (Max): 7.5

===========================================================================
AUSCERT External Security Bulletin Redistribution

ESB-2024.2406
ICS Advisory | ICSA-24-109-01 Unitronics Vision Series PLCs
19 April 2024

===========================================================================

AusCERT Security Bulletin Summary
———————————

Product: Unitronics Vision Series PLCs
Publisher: ICS-CERT
Operating System: Network Appliance
Resolution: Mitigation
CVE Names: CVE-2024-1480

Original Bulletin:
https://www.cisa.gov/news-events/ics-advisories/icsa-24-109-01

Comment: CVSS (Max): 7.5 CVE-2024-1480 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N)
CVSS Source: ICS-CERT
Calculator: https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

– ————————–BEGIN INCLUDED TEXT——————–

ICS Advisory (ICSA-24-109-01)

Unitronics Vision Series PLCs

Release Date
April 18, 2024

1. EXECUTIVE SUMMARY

o CVSS v4 8.7
o ATTENTION : Exploitable remotely/low attack complexity
o Vendor : Unitronics
o Equipment : Vision series PLCs
o Vulnerability : Storing Passwords in a Recoverable Format

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to log in
to the Remote HMI feature, where the PLC may be factory reset, stopped, and
restarted.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Unitronics Vision 230 PLCs are affected:

o Vision 230: All versions
o Vision 280: All versions
o Vision 290: All versions
o Vision 530: All versions
o Vision 120: All versions

3.2 Vulnerability Overview

3.2.1 Storing Passwords in a Recoverable Format CWE-257

Unitronics Vision Standard PLCs allow a remote, unauthenticated individual to
retrieve the ‘Information Mode’ password in plaintext.

CVE-2024-1480 has been assigned to this vulnerability. A CVSS v3.1 base score
of 7.5 has been calculated; the CVSS vector string is ( AV:N/AC:L/PR:N/UI:N/S:U
/C:H/I:N/A:N ).

A CVSS v4 score has also been calculated for CVE-2024-1480 . A base score of
8.7 has been calculated; the CVSS vector string is ( CVSS4.0/AV:N/AC:L/AT:N/
PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N ).

3.3 BACKGROUND

o CRITICAL INFRASTRUCTURE SECTORS: Water and Wastewater
o COUNTRIES/AREAS DEPLOYED: Worldwide
o COMPANY HEADQUARTERS LOCATION: Israel

3.4 RESEARCHER

Reid Wightman of Dragos reported this vulnerability to CISA.

4. MITIGATIONS

Dragos recommends users to restrict access to the PLC on TCP/20256 by either
changing the default programmer port, or apply a multi-factor VPN to protect
the service from remote access.

Unitronics has not responded to requests to work with CISA to mitigate this
vulnerability. Please contact Unitronics customer support for more information.

CISA recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities, such as:

o Minimize network exposure for all control system devices and/or systems,
ensuring they are not accessible from the internet .
o Locate control system networks and remote devices behind firewalls and
isolating them from business networks.
o When remote access is required, use more secure methods, such as virtual
private networks (VPNs), recognizing VPNs may have vulnerabilities and
should be updated to the most current version available. Also recognize VPN
is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices
on the ICS webpage on cisa.gov/ics . Several CISA products detailing cyber
defense best practices are available for reading and download, including
Improving Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies .

CISA encourages organizations to implement recommended cybersecurity strategies
for proactive defense of ICS assets .

Additional mitigation guidance and recommended practices are publicly available
on the ICS webpage at cisa.gov/ics in the technical information paper,
ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation
Strategies .

Organizations observing suspected malicious activity should follow established
internal procedures and report findings to CISA for tracking and correlation
against other incidents.

CISA also recommends users take the following measures to protect themselves
from social engineering attacks:

o Do not click web links or open attachments in unsolicited email messages.
o Refer to Recognizing and Avoiding Email Scams for more information on
avoiding email scams.
o Refer to Avoiding Social Engineering and Phishing Attacks for more
information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has
been reported to CISA at this time.

5. UPDATE HISTORY

o April 18, 2024: Initial Publication

This product is provided subject to this Notification and this Privacy & Use
policy.

Vendor

Unitronics

– ————————–END INCLUDED TEXT———————-

You have received this e-mail bulletin as a result of your organisation’s
registration with AusCERT. The mailing list you are subscribed to is
maintained within your organisation, so if you do not wish to continue
receiving these bulletins you should contact your local IT manager. If
you do not know who that is, please send an email to auscert@auscert.org.au
and we will forward your request to the appropriate person.

NOTE: Third Party Rights
This security bulletin is provided as a service to AusCERT’s members. As
AusCERT did not write the document quoted above, AusCERT has had no control
over its content. The decision to follow or act on information or advice
contained in this security bulletin is the responsibility of each user or
organisation, and should be considered in accordance with your organisation’s
site policies and procedures. AusCERT takes no responsibility for consequences
which may arise from following or acting on information or advice contained in
this security bulletin.

NOTE: This is only the original release of the security bulletin. It may
not be updated when updates to the original are made. If downloading at
a later date, it is recommended that the bulletin is retrieved directly
from the author’s website to ensure that the information is still current.

Contact information for the authors of the original document is included
in the Security Bulletin above. If you have any questions or need further
information, please contact them directly.

Previous advisories and external security bulletins can be retrieved from:

https://www.auscert.org.au/bulletins/

===========================================================================
Australian Computer Emergency Response Team
The University of Queensland
Brisbane
Qld 4072

Internet Email: auscert@auscert.org.au
Facsimile: (07) 3365 7031
Telephone: (07) 3365 4417 (International: +61 7 3365 4417)
AusCERT personnel answer during Queensland business hours
which are GMT+10:00 (AEST).
On call after hours for member emergencies only.
===========================================================================Security BulletinsRead More